Short-circuit or grounding at the drive output on this product. The manual's first action is: “Check the cables connecting the drive to the motor, and the insulation of the motor Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu. Reduce the switching frequency Connect chokes in series with the motor Check the adjustment of speed loop and brake”
- Model
- Schneider Altivar 61
- Display shows
- [Motor short circuit] (SCF1)
- Type
- Fault code
- Source
- Manual p. 241
What SCF1 means
[Motor short circuit] p. 241
Common causes
- Short-circuit or grounding at the drive output p. 241
What to do
- Check the cables connecting the drive to the motor, and the insulation of the motor Perform the diagnostic tests via the [1.10 DIAGNOSTICS] menu. Reduce the switching frequency Connect chokes in series with the motor Check the adjustment of speed loop and brake p. 241
Before you service the product, read the safety instructions in the manual p. 10.
If SCF1 is still not resolved
- Disconnect all power including external control power p. 4 “Disconnect all power including external control power that may be present before servicing the drive.”
This page summarises what the manufacturer’s manual says about SCF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.