Schneider Altivar 61 Error InFb: [Internal- th. sensor]

Schneider Altivar 61 · taken from the manufacturer’s manual, pages cited

Fault codeInFb

The drive temperature sensor or the braking unit's temperature sensor is not operating correctly on this product. The manual's first action is: “Replace the temperature sensor Inspect/repair the drive Replace the braking unit's temperature sensor Inspect/repair the braking unit The monitoring of this fault must be disabled by the [Brake res. fault Mgt] (bUb) parameter, page 206 if there is no braking unit connected to the drive”

Model
Schneider Altivar 61
Display shows
[Internal- th. sensor] (InFb)
Type
Fault code
Source
Manual p. 241

What InFb means

[Internal- th. sensor] p. 241

Common causes

  • The drive temperature sensor is not operating correctly The braking unit's temperature sensor is not operating correctly p. 241

What to do

  1. Replace the temperature sensor Inspect/repair the drive Replace the braking unit's temperature sensor Inspect/repair the braking unit The monitoring of this fault must be disabled by the [Brake res. fault Mgt] (bUb) parameter, page 206 if there is no braking unit connected to the drive p. 241

Before you service the product, read the safety instructions in the manual p. 10.

If InFb is still not resolved

  • Disconnect all power including external control power p. 4
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about InFb; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.