Fault codeLF1

PTC1 overhear means overheating of the PTC1 probes detected or PTC1 probes open or short-circuited. The manual's first action is: “Check the motor load and motor size”

Model
Schneider Altivar 61
Display shows
[PTC1 overhear] (LF1)
Type
Fault code
Source
Manual p. 244

What LF1 means

[PTC1 overhear] p. 244

Common causes

  • Overheating of the PTC1 probes detected p. 244
  • PTC1 probes open or short-circuited p. 244

What to do

  1. Check the motor load and motor size p. 244
  2. Check the motor ventilation p. 244
  3. Wait for the motor to cool before restarting p. 244
  4. Check the type and state of the PTC probes p. 244
  5. Check the PTC probes and the wiring between them and the motor/drive p. 244

Before you service the product, read the safety instructions in the manual p. 10.

If LF1 is still not resolved

  • Disconnect all power including external control power p. 4
    “Disconnect all power including external control power that may be present before servicing the drive.”

This page summarises what the manufacturer’s manual says about LF1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Schneider. Found a mistake? Report an error.