E9 on the Omron CS1W-CRM21/CJ1W-CRM21 is listed in the manual as: Memory access error. The manual's first action is: “Restart the Master Unit. If the same error occurs again, replace the Master Unit.”
- Model
- Omron CS1W-CRM21/CJ1W-CRM21
- Display shows
- Memory access error (E9)
- Type
- Error code
- Source
- Manual p. 209
What E9 means
Memory access error p. 209
Common causes
- One of the following errors occurred when the non-volatile memory in the Unit was accessed: 1) Not all 64 records could be used during initialization or when registering an error in the error history. 2) An error history reading or writing error. 3) A network parameters reading or writing failure during initialization. 4) An identity information reading failure during initialization. 5) A Registration Table information reading or writing failure during initialization. 6) A Software Setting Table information reading or writing failure during initialization. p. 209
What to do
- Restart the Master Unit. If the same error occurs again, replace the Master Unit. p. 209
Before you service the product, read the safety instructions in the manual p. 15.
If E9 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.