Severe fault alarm generates a user-defined fatal error that stops the PLC from running. The manual's first action is: “For CS1-H, CJ1-H, and CJ1M CPU units, FALS(007) can also be used to generate a fatal system error.”
- Model
- Omron CS/CJ series
- Display shows
- Severe fault alarm (FALS(007))
- Type
- Error code
- Source
- Manual p. 161
What FALS(007) means
Severe fault alarm p. 962
Common causes
- Generate a user-defined fatal error. A fatal error stops the PLC from running. p. 962
- When executing FALS(007) and N is set to a FALS number (1–511) that differs from the contents of A529 (the system-generated FAL/FALS number), a fatal error with that FALS number will be generated. p. 962
- When executing FALS(007) and N is set to a FAL number (1–511) that matches the contents of A529 (the generated FAL/FALS system number), a fatal error will be generated. p. 962
What to do
- For CS1-H, CJ1-H, and CJ1M CPU units, FALS(007) can also be used to generate a fatal system error. p. 962
- Generates a fatal error with that FALS number and performs the following procedures: 1. The FALS error flag (A40106) turns ON (the PLC stops running). 2. The error code is written to A400. For FAL numbers 0001–01FF (1–511), the error codes are C101–C2FF. 3. The error code and the date/time of the error occurrence are written to the error log area (A100–A199). 4. The ERR indicator on the CPU unit flashes. 5. If a word address is specified in S, ASCII information starting at S is recorded (displayed on external devices). p. 962
- The error code and detailed error code are specified in S and S+1. The following procedures are also performed. p. 962
Before you service the product, read the safety instructions in the manual p. 11.
If FALS(007) is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.
This page summarises what the manufacturer’s manual says about FALS(007); each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.