Omron CS/CJ series Error FALS(007): Severe fault alarm

Omron CS/CJ series programmable controller · taken from the manufacturer’s manual, pages cited

Error codeFALS(007)

Severe fault alarm generates a user-defined fatal error that stops the PLC from running. The manual's first action is: “For CS1-H, CJ1-H, and CJ1M CPU units, FALS(007) can also be used to generate a fatal system error.”

Model
Omron CS/CJ series
Display shows
Severe fault alarm (FALS(007))
Type
Error code
Source
Manual p. 161

What FALS(007) means

Severe fault alarm p. 962

Common causes

  • Generate a user-defined fatal error. A fatal error stops the PLC from running. p. 962
  • When executing FALS(007) and N is set to a FALS number (1–511) that differs from the contents of A529 (the system-generated FAL/FALS number), a fatal error with that FALS number will be generated. p. 962
  • When executing FALS(007) and N is set to a FAL number (1–511) that matches the contents of A529 (the generated FAL/FALS system number), a fatal error will be generated. p. 962

What to do

  1. For CS1-H, CJ1-H, and CJ1M CPU units, FALS(007) can also be used to generate a fatal system error. p. 962
  2. Generates a fatal error with that FALS number and performs the following procedures: 1. The FALS error flag (A40106) turns ON (the PLC stops running). 2. The error code is written to A400. For FAL numbers 0001–01FF (1–511), the error codes are C101–C2FF. 3. The error code and the date/time of the error occurrence are written to the error log area (A100–A199). 4. The ERR indicator on the CPU unit flashes. 5. If a word address is specified in S, ASCII information starting at S is recorded (displayed on external devices). p. 962
  3. The error code and detailed error code are specified in S and S+1. The following procedures are also performed. p. 962

Before you service the product, read the safety instructions in the manual p. 11.

If FALS(007) is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Omron service.

This page summarises what the manufacturer’s manual says about FALS(007); each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.