A Limit Inputs in Both Directions error occurs when limit signals for both directions are input simultaneously during origin search. The manual's first action is: “Check the wiring of the limit signals in both directions as well as the PLC Setup's Limit Signal Type setting (N.C. or N.O.) and execute the origin search again. Turn the power supply OFF and then ON if the signal type setting was changed.”
- Model
- Omron CJ1M-CPU22/CPU23
- Display shows
- Limit Inputs in Both Directions (0203)
- Type
- Error code
- Source
- Manual p. 148
What 0203 means
Limit Inputs in Both Directions p. 148
Common causes
- The origin search cannot be performed because the limit signals for both directions are being input simultaneously. p. 148
What to do
- Check the wiring of the limit signals in both directions as well as the PLC Setup's Limit Signal Type setting (N.C. or N.O.) and execute the origin search again. Turn the power supply OFF and then ON if the signal type setting was changed. p. 148
Before you service the product, read the safety instructions in the manual p. 11.
If 0203 is still not resolved
- consult your OMRON representative p. 11 “You must consult with your OMRON representative before applying a PLC System to the above-mentioned applications.”
This page summarises what the manufacturer’s manual says about 0203; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.