An Origin Input Signal Error occurs when the Origin Input Signal is detected during deceleration from the origin search's high speed. The manual's first action is: “An Origin Input Signal Error (error code 0202) will occur and the motor will decelerate to a stop.”
- Model
- Omron CJ1M-CPU22/CPU23
- Display shows
- Origin Input Signal Error (0202)
- Type
- Error code
- Source
- Manual p. 137
What 0202 means
Origin Input Signal Error p. 137
Common causes
- The Origin Input Signal will be detected during deceleration from the origin search's high speed. p. 137
- In this operating mode, the Origin Input Signal will be detected if it is received during this deceleration. p. 137
- In this operating mode, the Origin Input Signal will be detected if it is received during this deceleration p. 137
- During an origin search in operating mode 0, the Origin Input Signal was received during the deceleration started after the Origin Proximity Input Signal was received. p. 137
What to do
- An Origin Input Signal Error (error code 0202) will occur and the motor will decelerate to a stop. p. 137
- An Origin Input Signal Error (error code 0202) will be generated. In this case, the motor will decelerate to a stop. p. 137
- the motor will decelerate to a stop. p. 137
- Take one or both of the following steps so that the Origin Input Signal is received after deceleration is completed. •Increase the distance between the Origin Proximity Input Signal sensor and Origin Input Signal sensor. •Decrease the difference between the origin search's high speed and proximity speed settings. p. 137
Before you service the product, read the safety instructions in the manual p. 11.
If 0202 is still not resolved
- consult your OMRON representative p. 11 “You must consult with your OMRON representative before applying a PLC System to the above-mentioned applications.”
This page summarises what the manufacturer’s manual says about 0202; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Omron. Found a mistake? Report an error.