NORDAC SK 500E / SK 520E Error E005: D.C. link overvoltage

NORDAC SK 500E / SK 520E inverter · taken from the manufacturer’s manual, pages cited

Error codeE005

D.C. link overvoltage has occurred The manual's first action is: “Reduce recovered energy by providing a brake resistor”

Model
NORDAC SK 500E / SK 520E
Display shows
D.C. link overvoltage (E005)
Type
Error code
Source
Manual p. 16

What E005 means

D.C. link overvoltage p. 16

Common causes

  • Frequency inverter D.C. link voltage is too high p. 16
  • Extend braking time (P103) p. 16
  • Except for lifting gear applications the mode for a delayed disconnection (P108) could be set p. 16
  • Prolong the time set for "quick stopping" (P426) p. 16
  • Mains voltage is too high p. 16

Safety warnings — read before you start

  • DANGERDANGER. touching them may cause, due to the voltages at which they are operated, serious injuries or even death p. 1

What to do

  1. Reduce recovered energy by providing a brake resistor p. 16
  2. Please check the mains voltage 380V-20%...480V+10% or 200...240V ± 10% respectively p. 16

If E005 is still not resolved

  • contact service / dealer p. 16
    “Please check the mains voltage 380V-20%...480V+10% or 200...240V ± 10% respectively”

This page summarises what the manufacturer’s manual says about E005; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with NORDAC. Found a mistake? Report an error.