Error codeE005
D.C. link overvoltage has occurred The manual's first action is: “Reduce recovered energy by providing a brake resistor”
- Model
- NORDAC SK 500E / SK 520E
- Display shows
- D.C. link overvoltage (E005)
- Type
- Error code
- Source
- Manual p. 16
What E005 means
D.C. link overvoltage p. 16
Common causes
- Frequency inverter D.C. link voltage is too high p. 16
- Extend braking time (P103) p. 16
- Except for lifting gear applications the mode for a delayed disconnection (P108) could be set p. 16
- Prolong the time set for "quick stopping" (P426) p. 16
- Mains voltage is too high p. 16
Safety warnings — read before you start
- DANGERDANGER. touching them may cause, due to the voltages at which they are operated, serious injuries or even death p. 1
What to do
- Reduce recovered energy by providing a brake resistor p. 16
- Please check the mains voltage 380V-20%...480V+10% or 200...240V ± 10% respectively p. 16
If E005 is still not resolved
- contact service / dealer p. 16 “Please check the mains voltage 380V-20%...480V+10% or 200...240V ± 10% respectively”
This page summarises what the manufacturer’s manual says about E005; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with NORDAC. Found a mistake? Report an error.