Mitsubishi Electric FX5 Error 1A9DH: Offset/Gain setting value range error

PLC · taken from the manufacturer’s manual, pages cited

Error code1A9DH

A value outside the range was set to CH□ Offset setting value or CH□ Gain setting value. The manual's first action is: “Reset CH□ Offset setting value or CH□ Gain setting value to the following value. ■Voltage Offset value: -10000 to +9000 Gain value: -9000 to +10000 ■Current Offset value: -20000 to +17000 Gain value: -17000 to +30000”

Model
Mitsubishi Electric FX5
Display shows
Offset/Gain setting value range error (1A9DH)
Type
Error code
Source
Manual p. 62

What 1A9DH means

Offset/Gain setting value range error p. 62

Common causes

  • A value outside the range was set to CH□ Offset setting value or CH□ Gain setting value. p. 62

What to do

  1. Reset CH□ Offset setting value or CH□ Gain setting value to the following value. ■Voltage Offset value: -10000 to +9000 Gain value: -9000 to +10000 ■Current Offset value: -20000 to +17000 Gain value: -17000 to +30000 p. 62

Before you service the product, read the safety instructions in the manual p. 3.

If 1A9DH is still not resolved

  • contact service / dealer p. 3
    “It is important to follow all precautions for personal safety.”
  • contact service / dealer p. 4
    “Failure to do so may cause electric shock or damage to the product.”

This page summarises what the manufacturer’s manual says about 1A9DH; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Mitsubishi Electric. Found a mistake? Report an error.