Data logging error means detected an error in the memory board or log data. The manual's first action is: “Set 1 in the special internal output R7EC to clear the error code from the PLC. Pressing the reset switch for the power failure memory protection (R.CL) on the front of the CPU while the CPU is stopped also clears the error code. However, if the reset switch for the power failure memory protection is pressed, all the power failure memory area is cleared with 0, so exercise caution.”
- Model
- Hitachi EH-150
- Display shows
- Data logging error (A0)
- Type
- Error code
- Source
- Manual p. 432
What A0 means
Data logging error p. 432
Common causes
- Detected an error in the memory board or log data. p. 432
What to do
- Set 1 in the special internal output R7EC to clear the error code from the PLC. Pressing the reset switch for the power failure memory protection (R.CL) on the front of the CPU while the CPU is stopped also clears the error code. However, if the reset switch for the power failure memory protection is pressed, all the power failure memory area is cleared with 0, so exercise caution. p. 432
Before you service the product, read the safety instructions in the manual p. 3.
If A0 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Hitachi service.
This page summarises what the manufacturer’s manual says about A0; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Hitachi. Found a mistake? Report an error.