Hitachi EH-150 Error 71: Battery error [always checking]

Hitachi EH-150 · taken from the manufacturer’s manual, pages cited

Error code71

On the Hitachi EH-150, code 71 means a battery error that is always checked because the battery voltage dropped below the specified value or the battery is not installed. The manual's first action is: “Set 1 in the special internal output R7EC to clear the error code from the PLC. Pressing the reset switch for the power failure memory protection (R.CL) on the front of the CPU while the CPU is stopped also clears the error code. However, if the reset switch for the power failure memory protection is pressed, all the power failure memory area is cleared with 0, so exercise caution.”

Model
Hitachi EH-150
Display shows
Battery error [always checking] (71)
Type
Error code
Source
Manual p. 432

What 71 means

Battery error [always checking] p. 432

Common causes

  • Battery voltage dropped below specified value p. 432
  • Battery not installed p. 432

What to do

  1. Set 1 in the special internal output R7EC to clear the error code from the PLC. Pressing the reset switch for the power failure memory protection (R.CL) on the front of the CPU while the CPU is stopped also clears the error code. However, if the reset switch for the power failure memory protection is pressed, all the power failure memory area is cleared with 0, so exercise caution. p. 432

Before you service the product, read the safety instructions in the manual p. 3.

If 71 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Hitachi service.

This page summarises what the manufacturer’s manual says about 71; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Hitachi. Found a mistake? Report an error.