47 on the Hitachi EH-150 is listed in the manual as: I/O assignment points over [when power turns on, when RUN starts, during RUN when parameters changed]. The manual's first action is: “Stops *2”
- Model
- Hitachi EH-150
- Display shows
- 47
- Type
- Error code
- Source
- Manual p. 430
What 47 means
I/O assignment points over [when power turns on, when RUN starts, during RUN when parameters changed] p. 430
Common causes
- Number of CPU assignment slots exceeds 16 slots (EH-CPU208/308/516/448) Number of CPU assignment slots exceeds 8 slots (EH-CPU104) p. 430
What to do
- Stops *2 p. 430
- Perform I/O assignment so that the maximum I/O points of the CPU module are not exceeded. p. 430
Before you service the product, read the safety instructions in the manual p. 3.
If 47 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Hitachi service.
This page summarises what the manufacturer’s manual says about 47; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Hitachi. Found a mistake? Report an error.