GE Fuji AF-300 Mini™ Error Er1: Memory error

GE Fuji AF-300 Mini Drive · taken from the manufacturer’s manual, pages cited

Alarm codeEr1

Memory error occurred due to power interruption during data writing, high noise interference, or CPU malfunction. The manual's first action is: “CHECK Check whether pressing the key resets the alarm after the function code data are initialized by setting the data for function code H03 to 1. SUGGESTED ACTIONS – Return the initialized function code data to their previous settings, then restart the operation.”

Model
GE Fuji AF-300 Mini™
Display shows
Memory error (Er1)
Type
Alarm code
Source
Manual p. 79

What Er1 means

Memory error p. 92

Common causes

  • Power supply turned off while drive was writing data (especially initializing data), and residual control circuit voltage was not high enough to enable writing of data. p. 92
  • High intensity noise was applied to the drive while data (especially initializing data) was being written. p. 92
  • The CPU did not operate normally. p. 92

What to do

  1. CHECK Check whether pressing the key resets the alarm after the function code data are initialized by setting the data for function code H03 to 1. SUGGESTED ACTIONS – Return the initialized function code data to their previous settings, then restart the operation. p. 92
  2. CHECK Check if appropriate noise control measures have been implemented (e.g. correct grounding and routing of control and main circuit wires). Alternatively, perform the same check as described in (1) above. SUGGESTED ACTIONS – Improve noise control. Alternatively, return the initialized function code data to their previous settings, then restart the operation. p. 92
  3. CHECK Initialize the function code data by setting H03 to 1, then reset the alarm by pressing the key and check that the alarm is triggered. SUGGESTED ACTIONS – Replace malfunctioning printed circuit board (PCB). p. 92

Before you service the product, read the safety instructions in the manual p. 4.

If Er1 is still not resolved

  • Contact a qualified electrician for wiring p. 5
    “Wiring must only be performed only by a qualified electrician.”
  • Check that power is off before wiring p. 24
    “Check that the power is turned off before proceeding with any wiring Failure to do so may result in electric shock.”

This page summarises what the manufacturer’s manual says about Er1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with GE Fuji. Found a mistake? Report an error.