Data Save Error During Undervoltage occurs when DC link voltage drops rapidly during data save or strong noise is received from surroundings or the control circuit malfunctions. The manual's first action is: “Confirm time for DC link voltage drop when power is disconnected.”
- Model
- Fuji Electric FRENIC‑Multi
- Display shows
- Data Save Error During Undervoltage (ef)
- Type
- Error code
- Source
- Manual p. 158
What ef means
Data Save Error During Undervoltage p. 158
Common causes
- (1) During data save when power is disconnected, rapid drop in DC link voltage causes control circuit to drop rapidly p. 158
- (2) During data save when power is disconnected, strong noise received from surroundings p. 158
- (3) Control circuit malfunction p. 158
What to do
- Confirm time for DC link voltage drop when power is disconnected. p. 158
- Confirm methods to resolve noise (grounding status, control / main circuit wiring and settings). p. 158
- Confirm whether ef first occurred during power application. p. 158
Before you service the product, read the safety instructions in the manual p. 3.
If ef is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Fuji Electric service.
This page summarises what the manufacturer’s manual says about ef; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Fuji Electric. Found a mistake? Report an error.