Fuji Electric FRENIC‑Multi Error ef: Data Save Error During Undervoltage

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Error codeef

Data Save Error During Undervoltage occurs when DC link voltage drops rapidly during data save or strong noise is received from surroundings or the control circuit malfunctions. The manual's first action is: “Confirm time for DC link voltage drop when power is disconnected.”

Model
Fuji Electric FRENIC‑Multi
Display shows
Data Save Error During Undervoltage (ef)
Type
Error code
Source
Manual p. 158

What ef means

Data Save Error During Undervoltage p. 158

Common causes

  • (1) During data save when power is disconnected, rapid drop in DC link voltage causes control circuit to drop rapidly p. 158
  • (2) During data save when power is disconnected, strong noise received from surroundings p. 158
  • (3) Control circuit malfunction p. 158

What to do

  1. Confirm time for DC link voltage drop when power is disconnected. p. 158
  2. Confirm methods to resolve noise (grounding status, control / main circuit wiring and settings). p. 158
  3. Confirm whether ef first occurred during power application. p. 158

Before you service the product, read the safety instructions in the manual p. 3.

If ef is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Fuji Electric service.

This page summarises what the manufacturer’s manual says about ef; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Fuji Electric. Found a mistake? Report an error.