A ground fault has occurred, indicating the AC drive output is abnormal due to grounding or short circuit current exceeding the rated value. The manual's first action is: “1. Check whether the IGBT power module is damaged. 2. Check for possible poor insulation on the output wires or on the motor.”
- Model
- Eaton MVX9000
- Display shows
- GFF
- Type
- Fault code
- Source
- Manual p. 112
What GFF means
Ground fault: The AC drive output is abnormal. When the output terminal is grounded (short circuit current is 50% more than the AC drive rated current), the AC drive power module may be damaged. The short circuit protection is provided for AC drive protection, not user protection. p. 112
Common causes
- Ground fault: p. 112
What to do
- 1. Check whether the IGBT power module is damaged. 2. Check for possible poor insulation on the output wires or on the motor. p. 112