Delta VFD-M-D Error ocn: Over-current during constant speed operation

VFD-M-D AC motor drive · taken from the manufacturer’s manual, pages cited

Fault codeocn

Over-current during constant speed operation means the drive is drawing too much current while operating at constant speed. The manual's first action is: “Check for possible poor insulation at the output line.”

Model
Delta VFD-M-D
Display shows
Over-current during constant speed operation (ocn)
Type
Fault code
Source
Manual p. 142

What ocn means

Over-current during constant speed operation p. 142

Common causes

  • Short-circuit at motor output: p. 142
  • Sudden increase in motor loading: p. 142
  • AC motor drive output power is too small: p. 142

What to do

  1. Check for possible poor insulation at the output line. p. 142
  2. Check for possible motor stall. p. 142
  3. Replace the AC motor drive with the next higher power model. p. 142

Before you service the product, read the safety instructions in the manual p. 4.

If ocn is still not resolved

  • contact your dealer p. 4
    “If you have any questions, please contact your dealer.”