Over Torque 1 occurs when output current exceeds the over-torque detection threshold and time while parameter is set. The manual's first action is: “Check whether the motor is overloaded; verify that the motor rated current value (parameter 05‑01) is appropriate; increase motor capacity.”
- Model
- Delta CP2000
- Display shows
- Over Torque 1 (ot1)
- Type
- Alarm code
- Source
- Manual p. 335
What ot1 means
Over Torque 1 p. 335
Common causes
- An alarm occurs when the output current exceeds the over‑torque detection threshold parameter 06‑07 or 06‑10, and also exceeds the over‑torque detection time parameter 06‑08 or 06‑11, while parameter 06‑06 or 06‑09 is set to 2 or 4. p. 335
What to do
- Check whether the motor is overloaded; verify that the motor rated current value (parameter 05‑01) is appropriate; increase motor capacity. p. 335
Before you service the product, read the safety instructions in the manual p. 327.
If ot1 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ot1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.