Delta CP2000 Error ot1: Over Torque 1

Variable frequency drive · taken from the manufacturer’s manual, pages cited

Alarm codeot1

Over Torque 1 occurs when output current exceeds the over-torque detection threshold and time while parameter is set. The manual's first action is: “Check whether the motor is overloaded; verify that the motor rated current value (parameter 05‑01) is appropriate; increase motor capacity.”

Model
Delta CP2000
Display shows
Over Torque 1 (ot1)
Type
Alarm code
Source
Manual p. 335

What ot1 means

Over Torque 1 p. 335

Common causes

  • An alarm occurs when the output current exceeds the over‑torque detection threshold parameter 06‑07 or 06‑10, and also exceeds the over‑torque detection time parameter 06‑08 or 06‑11, while parameter 06‑06 or 06‑09 is set to 2 or 4. p. 335

What to do

  1. Check whether the motor is overloaded; verify that the motor rated current value (parameter 05‑01) is appropriate; increase motor capacity. p. 335

Before you service the product, read the safety instructions in the manual p. 327.

If ot1 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.