Fault code37
Drive control board is overheated. The fault trip limit is 88 °C. The manual's first action is: “Check for and correct: • Excessive ambient temperature. • Fan failure. • Obstructions in the air flow. Not for drives with an OMIO control board.”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- CB OVERTEMP (37)
- Type
- Fault code
- Source
- Manual p. 246
What 37 means
CB OVERTEMP p. 264
Common causes
- Drive control board is overheated. The fault trip limit is 88 °C. p. 264
What to do
- Check for and correct: • Excessive ambient temperature. • Fan failure. • Obstructions in the air flow. Not for drives with an OMIO control board. p. 264
Before you service the product, read the safety instructions in the manual p. 6.
If 37 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”