Incorrect input power and motor cable connection (i.e., input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a ". The manual's first action is: “This fault can be disabled by using parameter 3023 WIRING FAULT. • Check input power connections. Check grounding.”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- OUTP WIRING (35)
- Type
- Fault code
- Source
- Manual p. 246
What 35 means
OUTP WIRING p. 263
Common causes
- Incorrect input power and motor cable connection (i.e., input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a delta grounded system and the motor cable capacitance is large. p. 263
What to do
- This fault can be disabled by using parameter 3023 WIRING FAULT. • Check input power connections. Check grounding. p. 263
Before you service the product, read the safety instructions in the manual p. 6.
If 35 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”
This page summarises what the manufacturer’s manual says about 35; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.
