ABB ACS550-01 / ACS550-U1 Error 35: OUTP WIRING

ACS550-01/U1 drive · taken from the manufacturer’s manual, pages cited

Fault code35

Incorrect input power and motor cable connection (i.e., input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a ". The manual's first action is: “This fault can be disabled by using parameter 3023 WIRING FAULT. • Check input power connections. Check grounding.”

Model
ABB ACS550-01 / ACS550-U1
Display shows
OUTP WIRING (35)
Type
Fault code
Source
Manual p. 246

What 35 means

OUTP WIRING p. 263

Common causes

  • Incorrect input power and motor cable connection (i.e., input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a delta grounded system and the motor cable capacitance is large. p. 263

What to do

  1. This fault can be disabled by using parameter 3023 WIRING FAULT. • Check input power connections. Check grounding. p. 263

Before you service the product, read the safety instructions in the manual p. 6.

If 35 is still not resolved

  • contact your local ABB representative for replacement p. 6
    “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
  • For more technical information, contact your local ABB representative. p. 7
    “For more technical information, contact your local ABB representative.”