The drive is not detecting a valid encoder signal. The manual's first action is: “Check for and correct: • Encoder presence and proper connection (reverse wired = channel A connected to terminal of channel B or vice versa, loose connection or short circuit). • Voltage logic levels are outside of the specified range. • A working and properly connected Pulse Encoder Interface Module, O_TAC-01. • Wrong value entered in parameter 5001 PULSE NR. A wrong value will only be detected if the error is such that the calculated slip is greater than 4 times the rated slip of the motor. • Encoder is not being used, but parameter 5002 ENCODER ENABLE = 1 (ENABLE).”
- Model
- ABB ACS550-01 / ACS550-U1
- Display shows
- ENCODER ERR (23)
- Type
- Fault code
- Source
- Manual p. 245
What 23 means
ENCODER ERR p. 263
Common causes
- The drive is not detecting a valid encoder signal. p. 263
What to do
- Check for and correct: • Encoder presence and proper connection (reverse wired = channel A connected to terminal of channel B or vice versa, loose connection or short circuit). • Voltage logic levels are outside of the specified range. • A working and properly connected Pulse Encoder Interface Module, O_TAC-01. • Wrong value entered in parameter 5001 PULSE NR. A wrong value will only be detected if the error is such that the calculated slip is greater than 4 times the rated slip of the motor. • Encoder is not being used, but parameter 5002 ENCODER ENABLE = 1 (ENABLE). p. 263
Before you service the product, read the safety instructions in the manual p. 6.
If 23 is still not resolved
- contact your local ABB representative for replacement p. 6 “Never attempt to repair a malfunctioning drive; contact your local ABB representative for replacement.”
- For more technical information, contact your local ABB representative. p. 7 “For more technical information, contact your local ABB representative.”