ABB ACS310 Error 1026: PAR USER LOAD C

AC drive · taken from the manufacturer’s manual, pages cited

Fault code1026

Code 1026 means there is an incorrect user load curve parameter setting. The manual's first action is: “Check parameter settings. Following must apply: • 3704 LOAD FREQ 1 < 3707 LOAD FREQ 2 < 3710 LOAD FREQ 3 < 3713 LOAD FREQ 4 < 3716 LOAD FREQ 5 • 3705 LOAD TORQ LOW 1 < 3706 LOAD TORQ HIGH 1 • 3708 LOAD TORQ LOW 2 < 3709 LOAD TORQ HIGH 2 • 3711 LOAD TORQ LOW 3 < 3712 LOAD TORQ HIGH 3 • 3714 LOAD TORQ LOW 4 < 3715 LOAD TORQ HIGH 4 • 3717 LOAD TORQ LOW 5 < 3718 LOAD TORQ HIGH 5.”

Model
ABB ACS310
Display shows
PAR USER LOAD C (1026)
Type
Fault code
Source
Manual p. 316

What 1026 means

PAR USER LOAD C p. 316

Common causes

  • Incorrect user load curve parameter setting p. 316

What to do

  1. Check parameter settings. Following must apply: • 3704 LOAD FREQ 1 < 3707 LOAD FREQ 2 < 3710 LOAD FREQ 3 < 3713 LOAD FREQ 4 < 3716 LOAD FREQ 5 • 3705 LOAD TORQ LOW 1 < 3706 LOAD TORQ HIGH 1 • 3708 LOAD TORQ LOW 2 < 3709 LOAD TORQ HIGH 2 • 3711 LOAD TORQ LOW 3 < 3712 LOAD TORQ HIGH 3 • 3714 LOAD TORQ LOW 4 < 3715 LOAD TORQ HIGH 4 • 3717 LOAD TORQ LOW 5 < 3718 LOAD TORQ HIGH 5. p. 316

Before you service the product, read the safety instructions in the manual p. 340.

If 1026 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”