Fault code0035
Code 0035 means incorrect input power and motor cable connection, where the input power cable is connected to the drive motor connection. The manual's first action is: “Check input power connections.”
- Model
- ABB ACS310
- Display shows
- 0035
- Type
- Fault code
- Source
- Manual p. 313
What 0035 means
OUTP WIRING (FF95) 0306 bit 15 (programmable fault function 3023) p. 313
Common causes
- Incorrect input power and motor cable connection (ie, input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a delta grounded system and the motor cable capacitance is large. p. 313
What to do
- Check input power connections. p. 313
Before you service the product, read the safety instructions in the manual p. 340.
If 0035 is still not resolved
- contact your local ABB representative or Authorized Service Center for replacement p. 17 “contact your local ABB representative or Authorized Service Center for replacement”
This page summarises what the manufacturer’s manual says about 0035; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with ABB. Found a mistake? Report an error.
