ABB ACS310 Error 0035: OUTP WIRING (FF95) 0306 bit 15 (programmable fault function 3023)

AC drive · taken from the manufacturer’s manual, pages cited

Fault code0035

Code 0035 means incorrect input power and motor cable connection, where the input power cable is connected to the drive motor connection. The manual's first action is: “Check input power connections.”

Model
ABB ACS310
Display shows
0035
Type
Fault code
Source
Manual p. 313

What 0035 means

OUTP WIRING (FF95) 0306 bit 15 (programmable fault function 3023) p. 313

Common causes

  • Incorrect input power and motor cable connection (ie, input power cable is connected to drive motor connection). The fault can be erroneously declared if the drive is faulty or the input power is a delta grounded system and the motor cable capacitance is large. p. 313

What to do

  1. Check input power connections. p. 313

Before you service the product, read the safety instructions in the manual p. 340.

If 0035 is still not resolved

  • contact your local ABB representative or Authorized Service Center for replacement p. 17
    “contact your local ABB representative or Authorized Service Center for replacement”