SERIAL 1 ERR means fieldbus communication has timed out due to setup, settings, or line issues. The manual's first action is: “Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line.”
- Model
- ABB ACH550
- Display shows
- SERIAL 1 ERR (28)
- Type
- Fault code
- Source
- Manual p. 26
What 28 means
SERIAL 1 ERR p. 26
Common causes
- Fieldbus communication has timed out. p. 26
What to do
- Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51 or 53 as appropriate). • Poor connections and/or noise on line. p. 26
Before you service the product, read the safety instructions in the manual p. 2.
If 28 is still not resolved
- contact the factory or your local Authorized Service Center for repair or replacement. p. 2 “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”