Fault code22
SUPPLY PHASE indicates ripple voltage in DC link is too high due to missing phase, blown fuse, or external filter interaction. The manual's first action is: “Check for and correct: • Missing mains phase. • Blown fuse. • Interaction with external input filter. Set parameter 2619 to "ON".”
- Model
- ABB ACH550
- Display shows
- SUPPLY PHASE (22)
- Type
- Fault code
- Source
- Manual p. 26
What 22 means
SUPPLY PHASE p. 26
Common causes
- Ripple voltage in the DC link is too high. p. 26
What to do
- Check for and correct: • Missing mains phase. • Blown fuse. • Interaction with external input filter. Set parameter 2619 to "ON". p. 26
Before you service the product, read the safety instructions in the manual p. 2.
If 22 is still not resolved
- contact the factory or your local Authorized Service Center for repair or replacement. p. 2 “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”