ABB ACH550 Error 10: PANEL LOSS

AC drive · taken from the manufacturer’s manual, pages cited

Fault code10

PANEL LOSS means panel communication is lost, either due to local control mode or remote mode with parameterized start/stop functions. The manual's first action is: “To correct check: Communication lines and connections Parameter 3002 PANEL COMM ERROR. Parameters in Group 10: START/STOP(DIR) and Group 11: REFERENCE SELECT (if drive operation is AUTO).”

Model
ABB ACH550
Display shows
PANEL LOSS (10)
Type
Fault code
Source
Manual p. 25

What 10 means

PANEL LOSS p. 25

Common causes

  • Panel communication is lost and either: Drive is in local control mode (the control panel displays HAND or OFF), or Drive is in remote control mode (AUTO) and is parameterized to accept start/stop, direction or reference from the control panel. p. 25

What to do

  1. To correct check: Communication lines and connections Parameter 3002 PANEL COMM ERROR. Parameters in Group 10: START/STOP(DIR) and Group 11: REFERENCE SELECT (if drive operation is AUTO). p. 25

Before you service the product, read the safety instructions in the manual p. 2.

If 10 is still not resolved

  • contact the factory or your local Authorized Service Center for repair or replacement. p. 2
    “Never attempt to repair a malfunctioning ACH550; contact the factory or your local Authorized Service Center for repair or replacement.”