Sunways STT 4~25kW Series Manuals

ManualLib has 2 documents for the Sunways STT 4~25kW Series (inverter): 1 installation guide, 1 user manual. Every file can be read online or downloaded as a PDF for free.

Installation Guide 1User Manual 1

Key facts

Brand
Sunways
Model
STT 4~25kW Series
Category
inverter
Industry
Electronics
Documents
2
Languages
EN
Last added
2026-11-20

Start here

STT 4-25kW series three-phase inverter user manual

STT 4-25kW series three-phase inverter user manual

User Manual 16 pages · 2.5 MB · EN

The Sunways STT 4–25kW series is a three-phase grid-connected PV inverter that converts DC power from PV strings into AC power for the grid. The manual covers safety instructions, product introduction, installation, electrical connection, start/stop, display operation, troubleshooting, and technical parameters.

It lists ten models from STT-4KTL to STT-25KTL and describes applicable TN-S, TN-C, TN-C-S, IT and TT grids. Installation guidance includes location, mounting, electrical connection, monitoring device installation, and the packing list.

Read online

Sunways STT 4~25kW Series specifications

Product seriesSTT 4~25kW series three-phase grid-connected PV inverter with dual MPPT
ModelsSTT-4KTL, STT-5KTL, STT-6KTL, STT-8KTL, STT-10KTL, STT-12KTL, STT-15KTL, STT-17KTL, STT-20KTL, STT-25KTL
AC breakerRequired on the AC side of the inverter
PV cable cross-section2.5-4 mm²
PV cable strip length7 mm
AC cable sheath strip length50 mm
AC wire end strip length8 mm
Wall mounting drill bit diameter10 mm
Wall mounting hole depth80 mm
Wall mounting holes5 holes
WiFi frequency support2.4 GHz only
WiFi configuration addresshttp://10.10.100.254
WiFi module login credentialsUsername and password are both admin

Source: Sunways STT 4~25kW Series Three-Phase Grid-Connected PV Inverter Quick Installation Guide

All Sunways STT 4~25kW Series documents by type

Installation Guide 1

Mounting, wiring and first power-up. Read it before the hardware goes in.

User Manual 1

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What position must the DC switch be in when connecting the PV connectors?

It must be switched to the OFF position.

From: Sunways STT 4~25kW Series Three-Phase Grid-Connected PV Inverter Quick Installation Guide

Why must the inverter be well-grounded?

For resisting surge voltage shock and improving EMI performance.

From: Sunways STT 4~25kW Series Three-Phase Grid-Connected PV Inverter Quick Installation Guide

What grid types does the Sunways STT 4–25kW series support?

The applicable grid types are TN-S, TN-C, TN-C-S, IT and TT.

From: STT 4-25kW series three-phase inverter user manual

How many models are in the Sunways STT 4–25kW series?

The series contains 10 models, listed from STT-4KTL to STT-25KTL.

From: STT 4-25kW series three-phase inverter user manual