Schmersal SRB 301MC Manuals

ManualLib has 2 documents for the Schmersal SRB 301MC (Automation control Equipment): 2 user manuals. Every file can be read online or downloaded as a PDF for free.

User Manual 2

Key facts

Model
SRB 301MC
Documents
2
Languages
EN · PT
Last added
2023-11-11

Start here

Schmersal SRB 301MC / SRB 301MC-ST Safety-Monitoring Module Operating Instructions

Schmersal SRB 301MC / SRB 301MC-ST Safety-Monitoring Module Operating Instructions

User Manual 8 pages · 363 KB · EN

These operating instructions describe the SRB 301MC and SRB 301MC-ST safety-monitoring modules, which are designed for integration in safety circuits and for fitting in control cabinets. They are used for the safe evaluation of signals from positive break position switches or magnetic safety sensors on sliding, hinged and removable safety guards, as well as emergency stop control devices and AOPDs. The manual covers the SRB 301MC with screw connection and the SRB 301MC-ST with plug-in screw connection.

The document is intended for authorised qualified personnel and provides information on mounting, electrical connection, operating principle, set-up, maintenance, disassembly and disposal. It includes technical data, safety classification (PL e, SIL 3), LED and terminal descriptions, and wiring examples in the appendix.

Read online

Schmersal SRB 301MC specifications

Rated operating voltage Ue24 VDC −15% / +20% or 24 VAC −15% / +10%, 50/60 Hz
Power consumptionmax. 2.0 W / 4.9 VA
Safety classificationPL up to e, control category up to 4, SIL up to 3, PFH ≤ 2.00 × 10-8/h
Number of safety contacts3 safety contacts, 1 auxiliary contact
Max. switching capacity of safety contactsmax. 250 V, 8 A ohmic
Dimensions (H x W x D)SRB 301MC: 100 x 22.5 x 121 mm; SRB 301MC-ST: 120 x 22.5 x 121 mm
Weight230 g
Ambient temperature−25 °C … +60 °C
Protection classEnclosure IP40, terminals IP20, clearance IP54
MountingSnaps onto standard DIN rail to EN 60715
Cable sectionmin. 0.25 mm² / max. 2.5 mm²
Monitored inputsCross-wire, wire breakage and earth leakage detection

Source: Schmersal SRB 301MC / SRB 301MC-ST Safety-Monitoring Module Operating Instructions

All Schmersal SRB 301MC documents by type

User Manual 2

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What are the SRB 301MC and SRB 301MC-ST used for?

They are safety-monitoring modules for integration in safety circuits, used for the safe evaluation of signals from positive break position switches or magnetic safety sensors, emergency stop control devices and AOPDs.

From: Schmersal SRB 301MC / SRB 301MC-ST Safety-Monitoring Module Operating Instructions

What is the difference between the SRB 301MC and SRB 301MC-ST?

The SRB 301MC has a screw connection, while the SRB 301MC-ST has a plug-in screw connection; the ST version is also slightly taller at 120 mm versus 100 mm.

From: Schmersal SRB 301MC / SRB 301MC-ST Safety-Monitoring Module Operating Instructions

What are the safety outputs of the SRB 301MC?

The safety outputs are 13-14, 23-24 and 33-34; they open when inputs S11-S12 and/or S21-S22 open.

From: Schmersal SRB 301MC Safety Relay Instruction Manual

What performance level does the SRB 301MC meet?

Category 4, PL e according to DIN EN ISO 13849-1.

From: Schmersal SRB 301MC Safety Relay Instruction Manual