Key facts
- Brand
- Eurotherm
- Model
- 3216
- Category
- Industrial Robot
- Industry
- Industrial
- Documents
- 2
- Languages
- EN
- Last added
- 2026-10-19
Start here

Eurotherm 3116 and 3216 PID Temperature Controllers Engineering Handbook
This engineering handbook covers the complete setup and operation of the Eurotherm 3116 and 3216 PID temperature controllers. It guides users through installation, wiring, parameter configuration, calibration, and troubleshooting, with detailed diagrams and step‑by‑step instructions.
Key sections include installation and basic operation, wiring details, input/output configuration, control and tuning methods, alarm handling, timer functions, digital communications (RS232/RS485), and a full technical specification appendix.
Eurotherm 3216 specifications
| Ambient Temperature | 0 to 55oC (32 - 122oF) |
|---|---|
| Panel Thickness | up to 15mm |
| Wire Size | 0.5 to 1.5 mm (16 to 22AWG) |
| Terminal Torque | 0.4Nm (3.5lb in) |
| Line Supply | 85 - 264Vac 50/60Hz |
| Low Voltage Supply | 24Vac/dc |
| RTD Line Resistance Limit | 22 Ω |
| Input Resistance (Volts) | 100K Ω |
| Burden Resistor (mA) | 2.49 Ω |
| Relay Rating | 2A 264Vac resistive |
| Logic Output Level | 12Vdc at 5 to 40mA |
| CT Input Current | 0 to 50mA rms |
| CT Input Accuracy | 4% of reading |
| Digital Input Contact Closure | 12V @ 5-40mA |
| Maximum Continuous Voltage | 264Vac |
Source: Eurotherm 3216 Temperature Controller Installation and Basic Operation Guide
All Eurotherm 3216 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the maximum ambient temperature for the Eurotherm 3216?
The instrument is designed for use in an ambient temperature range of 0 to 55°C (32 - 122°F).
From: Eurotherm 3216 Temperature Controller Installation and Basic Operation Guide
What wire sizes are accepted by the screw terminals?
The screw terminals accept wire sizes from 0.5 to 1.5 mm, which corresponds to 16 to 22 AWG.
From: Eurotherm 3216 Temperature Controller Installation and Basic Operation Guide
How do I set up digital communications?
Connect the controller via RS232 for direct PC communication or RS485 for daisy‑chaining to additional controllers, following the wiring diagram in the digital communications section.
From: Eurotherm 3116 and 3216 PID Temperature Controllers Engineering Handbook