This user guide provides step-by-step instructions for installing, wiring, and configuring the Eurotherm 3216 Temperature Controller, including safety…
This document serves as a user guide for the Eurotherm 3216 Temperature Controller, covering installation, wiring, configuration, and basic operation. It details the physical dimensions, panel mounting procedures, and removal methods for the device. The guide also explains how to interpret the ordering code and hardware configuration labels found on the unit.
The manual provides comprehensive wiring instructions for various inputs and outputs, including thermocouples, RTDs, linear inputs, relays, and digital communications (RS232/RS485). It includes specific safety requirements for installation, such as enclosure standards, power isolation, and EMC compliance, along with an example wiring diagram.
| Ambient Temperature | 0 to 55oC (32 - 122oF) |
|---|---|
| Panel Thickness | up to 15mm |
| Wire Size | 0.5 to 1.5 mm (16 to 22AWG) |
| Terminal Torque | 0.4Nm (3.5lb in) |
| Line Supply | 85 - 264Vac 50/60Hz |
| Low Voltage Supply | 24Vac/dc |
| RTD Line Resistance Limit | 22 Ω |
| Input Resistance (Volts) | 100K Ω |
| Burden Resistor (mA) | 2.49 Ω |
| Relay Rating | 2A 264Vac resistive |
| Logic Output Level | 12Vdc at 5 to 40mA |
| CT Input Current | 0 to 50mA rms |
| CT Input Accuracy | 4% of reading |
| Digital Input Contact Closure | 12V @ 5-40mA |
| Maximum Continuous Voltage | 264Vac |
The instrument is designed for use in an ambient temperature range of 0 to 55°C (32 - 122°F).
The screw terminals accept wire sizes from 0.5 to 1.5 mm, which corresponds to 16 to 22 AWG.
The line resistance must not be greater than 22 Ω, or it may cause measurement errors.
The optional Output AA is a changeover relay (Form C) rated for 2A at 264Vac resistive.