Delta-T Devices GP2 Advanced Data Acquisition Data Logger Controller User Manual
The Delta-T Devices GP2 is an advanced data acquisition controller with 12 differential analog input channels (or 24 single-ended), four event/digital counter channels, one WET sensor serial input and two output relays that can be expanded to six. It stores about 2.5 million readings, reads sensors at intervals from 1 second to over 1000 days, and supports calculated measurements, user-defined variables and relay control based on thresholds or logic.
This version 1.0 user manual covers unboxing, an overview of the layout, channels, sensor supply and status LED, installing DeltaLINK 3 and connecting to the GP2, creating a simple program in six steps, the GP2 simulator, retrieving and importing logged data, plus appendices on the relay expansion module, network wiring, extension enclosures and mounting kits, followed by GP2 specifications, product care, the calibration certificate and legal information. This manual is written in Chinese.
Delta-T Devices GP2 specifications
| Analog input channels | 12 differential (or 24 single-ended) |
|---|---|
| Event / digital counter channels | 4 |
| Output relays | 2, expandable to 6 with the relay expansion module |
| Read interval | 1 second to over 1000 days |
| Reading storage capacity | about 2.5 million readings |
| Relay contact rating | up to 1 A (24 VAC or 32 V DC) |
| Analog input signal range | nominal 0 to 2.5 V, full range -1.4 to +2.7 V |
| Sensor supply | 3 V (±0.2 mV) or 5-10.5 V unregulated, plus 5 V (±2%) and 12 V (±0.4 V) terminals |
| Event channel frequency | events 1-2: pulses up to 30 kHz; events 3-4: pulses under 100 Hz |
Source: Delta-T Devices GP2 Advanced Data Acquisition Data Logger Controller User Manual
All Delta-T Devices GP2 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
How do I connect the GP2 to my PC?
Connect the GP2 to the PC with the supplied serial cable (GP2-USB or GP2-RS232) and run DeltaLINK. If the logger is not detected, use Detect USB Port or pick the COM port from the list.
From: Delta-T Devices GP2 Advanced Data Acquisition Data Logger Controller User Manual
What does the GP2 status LED indicate?
Two flashes every ten seconds mean the GP2 is logging, four flashes mean an error, and no flashing means no logging or no battery power.
From: Delta-T Devices GP2 Advanced Data Acquisition Data Logger Controller User Manual
What does the Status LED indicate?
Two flashes per ten seconds means the GP2 is logging, while four flashes in a group indicate an error.
From: Delta-T Devices GP2 Data Logger Controller User Manual
How do I perform a cold reset?
Hold the Reset button for more than 5 seconds until a second set of four LED flashes occur.
From: Delta-T Devices GP2 Data Logger Controller User Manual