CHINT NVF5 Series Variable Frequency Drive User Manual
The CHINT NVF5 series variable frequency drive utilizes sensorless vector control technology to provide precise control for various industrial applications, including textile, machine tools, and automation equipment. It features functions such as voltage stabilization, torque limiting, and simple PLC capabilities, with support for RS485 communication and expandable Ethernet or Profibus-DP interfaces. This manual is written in Chinese.
Read onlineChint NVF5 specifications
| Power Range | 0.4kW~22kW |
|---|---|
| Output Frequency Range | 0Hz-400Hz |
| Control Methods | Sensorless Vector Control, V/F Control |
| Starting Torque (0.5Hz) | 150% rated torque |
| Overload Capability | 150% current for 1 min, 180% for 2 sec |
| Speed Control Accuracy (Vector) | ±0.5% |
All Chint NVF5 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the rated working voltage for the Chint NVF5 inverter?
The rated working voltage is 230V for single-phase and 380V to 440V for three-phase.
What is the power range of the Chint NVF5 series inverter?
The power range is from 0.4kW to 22kW.
What is the maximum altitude for full rated power output?
The inverter can output its rated power at altitudes below 1000m.
From: Chint NVF5 Series Simple Vector Inverter Product Leaflet
What is the speed control accuracy for open-loop vector control?
The speed control precision is ±0.5% of the maximum speed.
From: Chint NVF5 Series Simple Vector Inverter Product Leaflet
What communication protocols does the NVF5 series support?
It supports standard RS485 and can be expanded with Ethernet, Profibus-DP, Devicenet, and CANopen.
From: CHINT NVF5 Series Variable Frequency Drive User Manual
What is the recommended insulation resistance for the motor before connection?
The insulation resistance should not be less than 5MΩ when tested with a 500V megohmmeter.
From: CHINT NVF5 Series Variable Frequency Drive User Manual