Chint JKF8 Series Intelligent Low Voltage Reactive Power Automatic Compensation Controller User Manual
The document describes the Chint JKF8 Series Intelligent Low Voltage Reactive Power Automatic Compensation Controller, designed for use with low-voltage parallel capacitor banks in 380V, 50Hz distribution systems. It features automatic capacitor switching to improve voltage quality and reduce energy loss, utilizing composite control of reactive power and power factor. This manual is written in Chinese.
Read onlineChint JKF8 specifications
| Rated Voltage | 380 V |
|---|---|
| Frequency | 50 Hz |
| Operating Temperature | -10℃~+40℃ |
| Relative Humidity | ≤50% at 40℃ |
| Altitude | ≤2000m |
| Output Contact Capacity | 380V 3A (Resistive) |
| Measurement Accuracy (Voltage) | ≤±1% |
| Power Consumption | <5W |
All Chint JKF8 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What is the application range of the JKF8 controller?
It is used with low-voltage parallel capacitor banks in 380V, 50Hz distribution systems to control automatic capacitor switching.
How does the controller handle low voltage conditions?
When grid voltage drops below 300V or exceeds the set value, it automatically and quickly cuts off the capacitors in stages within 5 seconds.
What is the installation opening size for this controller?
The embedded mounting hole dimension is 113×113mm.
From: Chint JKF8 Series Intelligent Low-Voltage Reactive Power Compensation Controller User Manual
What are the operating conditions regarding humidity?
Relative humidity must be ≤50% at 40℃ and ≤90% at 20℃.
From: Chint JKF8 Series Intelligent Low-Voltage Reactive Power Compensation Controller User Manual