Carrier 25HCE4 Manuals

ManualLib has 2 documents for the Carrier 25HCE4 (Other): 2 installation guides. Every file can be read online or downloaded as a PDF for free.

Installation Guide 2

Key facts

Brand
Carrier
Model
25HCE4
Category
Other
Documents
2
Languages
EN
Last added
2026-10-28

Start here

Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions

Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions

Installation Guide 12 pages · 549 KB · EN

This document provides installation instructions for Carrier 25HBC5, 25HCC5, and 25HCE4 single-stage heat pumps with Puron/C0114 refrigerant, rated from 1-1/2 to 5 nominal tons. It outlines critical safety considerations regarding electrical shock and explosion hazards, emphasizing the need for qualified installers and adherence to local electrical codes.

Read online

Carrier 25HCE4 specifications

Cooling Mode Minimum Outdoor Operating Ambient55°F (12.78°C)
Cooling Mode Maximum Outdoor Operating Ambient125°F (51.67°C)
Heating Mode Maximum Outdoor Operating Ambient66°F (18.89°C)
Maximum Liquid-Line Size3/8-in. OD
Unit Leveling Tolerance+2° (+3/8 in/ft,£9.5 mm/m)
Clearance to Service End24 in. (609.6 mm)
Clearance Above Unit48 in. (1219.2 mm)
Refrigerant TypePuron

Source: Carrier 25HBC5, 25HCE4 Single Stage Heat Pump Installation Guide

All Carrier 25HCE4 documents by type

Installation Guide 2

Mounting, wiring and first power-up. Read it before the hardware goes in.

Questions answered in these manuals

What refrigerant do these heat pumps use?

These units use Puron /C0114 Refrigerant.

From: Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions

Where should the defrost thermostat be located?

The defrost thermostat should be located on the 3/8 in. O.D. stub tube at the end of one of the feeder tubes going into the outdoor coil.

From: Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions

What is the minimum outdoor operating ambient for cooling mode?

The minimum outdoor operating ambient in cooling mode without an accessory is 55°F (12.78°C).

From: Carrier 25HBC5, 25HCE4 Single Stage Heat Pump Installation Guide

What is the maximum outdoor operating ambient for heating mode?

The maximum outdoor operating ambient in heating mode is 66°F (18.89°C).