Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions
This document provides installation instructions for Carrier 25HBC5, 25HCC5, and 25HCE4 single-stage heat pumps with Puron/C0114 refrigerant, rated from 1-1/2 to 5 nominal tons. It outlines critical safety considerations regarding electrical shock and explosion hazards, emphasizing the need for qualified installers and adherence to local electrical codes.
Read onlineCarrier 25HCE4 specifications
| Cooling Mode Minimum Outdoor Operating Ambient | 55°F (12.78°C) |
|---|---|
| Cooling Mode Maximum Outdoor Operating Ambient | 125°F (51.67°C) |
| Heating Mode Maximum Outdoor Operating Ambient | 66°F (18.89°C) |
| Maximum Liquid-Line Size | 3/8-in. OD |
| Unit Leveling Tolerance | +2° (+3/8 in/ft,£9.5 mm/m) |
| Clearance to Service End | 24 in. (609.6 mm) |
| Clearance Above Unit | 48 in. (1219.2 mm) |
| Refrigerant Type | Puron |
Source: Carrier 25HBC5, 25HCE4 Single Stage Heat Pump Installation Guide
All Carrier 25HCE4 documents by type
Mounting, wiring and first power-up. Read it before the hardware goes in.
Questions answered in these manuals
What refrigerant do these heat pumps use?
These units use Puron /C0114 Refrigerant.
From: Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions
Where should the defrost thermostat be located?
The defrost thermostat should be located on the 3/8 in. O.D. stub tube at the end of one of the feeder tubes going into the outdoor coil.
From: Carrier 25HBC5, 25HCC5, 25HCE4 Heat Pump Installation Instructions
What is the minimum outdoor operating ambient for cooling mode?
The minimum outdoor operating ambient in cooling mode without an accessory is 55°F (12.78°C).
From: Carrier 25HBC5, 25HCE4 Single Stage Heat Pump Installation Guide
What is the maximum outdoor operating ambient for heating mode?
The maximum outdoor operating ambient in heating mode is 66°F (18.89°C).