BW Technologies GP-MBUS4 Manuals

ManualLib has 3 documents for the BW Technologies GP-MBUS4: 1 installation guide, 2 user manuals. Every file can be read online or downloaded as a PDF for free.

Installation Guide 1User Manual 2

Key facts

Model
GP-MBUS4
Documents
3
Languages
EN
Last added
2023-10-15

Start here

BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

User Manual 20 pages · 192 KB · EN

The BW GasPoint MODBUS Expansion Module, model GP-MBUS4, is an optional add-on card for the 12-bit version of the BW GasPoint. It enables the device to interface with a MODBUS system using a suitable controller (master device). The module is fully compatible with BW GasPoint Monitors having serial numbers starting with '3-' and up.

Read online

BW Technologies GP-MBUS4 specifications

Communications ProtocolMODBUS RTU slave
Baud rates1200, 2400, 9600, 19200 bps field selectable
Word length8 bits
Electrical interfaceRS 485
Duplex modeHalf Duplex (2 or 4 wire field selectable)
MODBUS addressable range1-247
Max devices on network32
Supported Function Codes3, 5, 6, and 7
Power SupplyPowered by BW GasPoint
Power Consumption<70 mA @ 24 VDC

Source: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

All BW Technologies GP-MBUS4 documents by type

Installation Guide 1

Mounting, wiring and first power-up. Read it before the hardware goes in.

User Manual 2

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in these manuals

What is the default baud rate for the GP-MBUS4?

The default baud rate setting is 9600 bps.

From: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

What is the default parity configuration?

The default configuration is even parity with one stop bit.

From: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

What is the default baud rate for the GP-MBUS4?

The default baud rate setting is 9600.

From: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

What is the default parity configuration?

The default configuration is even parity with one stop bit.

From: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

What is the default baud rate for the GP-MBUS4?

The default baud rate is set to 9600.

From: BW Technologies GP-MBUS4 MODBUS Expansion Module Installation and Setup Instructions

What is the default slave address for the module?

The default slave address is set to 01.