AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual
The AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual serves as a guide for owners and qualified service personnel. It covers the operation of self-contained units designed for outdoor installation, utilizing natural or propane gas, electric resistance, steam, or hot water for heating, and direct expansion (DX) cooling. The document emphasizes safety protocols regarding gas usage, electrical power, and refrigerant management to prevent fire, explosion, or personal injury.
Read onlineAAON 1 RM SERIES specifications
| Heating Gas Supply Pressure (Natural) | 6" to 10.5" Water Column |
|---|---|
| Heating Gas Supply Pressure (Propane) | 11" to 12" Water Column |
| Manifold Pressure (Natural Gas) | 3.2" to 3.5" |
| Minimum Compressor Cycle Time | 4 minutes |
| Maximum Cycle Rate | 8 starts per hour |
| Cooling Season Minimum Outdoor Temperature | 55°F |
Source: AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual
All AAON 1 RM SERIES documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Mounting, wiring and first power-up. Read it before the hardware goes in.
Questions answered in these manuals
What should I do if I smell gas?
Immediately call your gas supplier from a neighbor's phone or call the fire department if you cannot reach the supplier. Do not use any phone in your building.
From: AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual
Can I cut off the main power supply to the unit during the cooling season?
No, you should never cut off the main power supply except for a complete shutdown, as this can cause liquid refrigerant migration and compressor damage.
From: AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual
What is the minimum height required for the curb when installing these units on a combustible roof?
The units are certified for installation on a combustible roof with a minimum of 12" high curb.
From: AAON 1RM Series Heating, Cooling and Combination Rooftop Units Installation Instructions
What is the maximum number of compressor starts allowed per hour during operation?
The cycle rate must not exceed 8 starts per hour to prevent compressor damage.
From: AAON 1RM Series Heating, Cooling and Combination Rooftop Units Installation Instructions