This manual contains all the information about 1 RM series heating/cooling&combination rooftop units, including how to use and maintain them.
The AAON 1 RM Series Heating/Cooling & Combination Rooftop Units Users Information Manual serves as a guide for owners and qualified service personnel. It covers the operation of self-contained units designed for outdoor installation, utilizing natural or propane gas, electric resistance, steam, or hot water for heating, and direct expansion (DX) cooling. The document emphasizes safety protocols regarding gas usage, electrical power, and refrigerant management to prevent fire, explosion, or personal injury.
| Heating Gas Supply Pressure (Natural) | 6" to 10.5" Water Column |
|---|---|
| Heating Gas Supply Pressure (Propane) | 11" to 12" Water Column |
| Manifold Pressure (Natural Gas) | 3.2" to 3.5" |
| Minimum Compressor Cycle Time | 4 minutes |
| Maximum Cycle Rate | 8 starts per hour |
| Cooling Season Minimum Outdoor Temperature | 55°F |
Immediately call your gas supplier from a neighbor's phone or call the fire department if you cannot reach the supplier. Do not use any phone in your building.
No, you should never cut off the main power supply except for a complete shutdown, as this can cause liquid refrigerant migration and compressor damage.
Turn off the main manual gas shut-off valve and disconnect the main electrical power to the unit.
Installation and service must be performed by a qualified installer, service agency, or the gas supplier.