Yokogawa UT35A/UT32A Digital Indicating Controller General Specifications

Yokogawa UT35A and UT32A digital indicating controllers with 14-segment color LCD, ladder sequence, Ethernet and single-loop PID control.


Yokogawa UT35A/UT32A Digital Indicating Controller General Specifications - cover page
Brand
YOKOGAWA
Category
Other products
Document type
Product Leaflet
Language
English
Pages
14
File format
PDF
File size
2.8 MB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
9A021FFAEFFBAFC9087536BAC544B61A

About this manual

Yokogawa UT35A and UT32A are digital indicating controllers of panel mounting type. They use a 14-segment color LCD display with navigation keys and include a ladder sequence function as standard.

The controllers provide single-loop control with a 200 ms control period. Features include universal I/O, retransmission output, PID and heating/cooling control, and Ethernet communication; a DIN rail mounting type is available with option code /MDL.

What's inside

  • Overview
  • Features
  • Control Computation Function
  • Alarm Functions
  • Ladder Sequence Function
  • Communication Function
  • Physical Interface

Specifications

Control modeSingle-loop control
Control period200 ms
Display14-segment color LCD
Panel depth65 mm
Ladder program capacity300 steps
Digital input points (UT35A)Up to 7
Digital input points (UT32A)Up to 4
Digital output points (UT35A)Up to 8
Digital output points (UT32A)Up to 5
Ethernet interfaceIEEE802.3 (10BASE-T, 100BASE-TX)
RS-485 maximum distance1200 m
Enclosure ratingNEMA4 (hose-down test only)

Frequently asked questions

What control mode do the UT35A and UT32A provide?

Single-loop control.

What is the control period?

200 ms.

Is the ladder sequence function standard?

Yes, it is included as standard.

What display is used?

A 14-segment color LCD display.