Troubleshooting guide for Error ID 66116 on Unified FB10000 Cooler, covering water pump, phase, valve, filter, pipe, sensor, and pump issues.
This manual addresses Error ID 66116 for the Unified FB10000 Cooler, detailing steps to resolve issues related to water flow. It covers checking circuit breaker thresholds, phase connections, external valves, water filters, pipe connections, and pump wiring. If all checks fail, it advises contacting an HP regional specialist. The guide is structured as a step-by-step diagnostic process for technicians. This manual is written in Chinese.
The CB threshold settings should be 6.3A for 50Hz and 8A for 60Hz.
Use an Ammeter to check connections TB_DIS 16,17,18. All three TBs should receive current.
This might indicate that the motor pump itself is faulty. In this case, replace the motor pump.