Unified FB10000 Cooler Critical Flow Rate Troubleshooting Manual
This manual addresses Error ID 66116 for the Unified FB10000 Cooler, detailing steps to resolve issues related to water flow. It covers checking circuit breaker thresholds, phase connections, external valves, water filters, pipe connections, and pump wiring. If all checks fail, it advises contacting an HP regional specialist. The guide is structured as a step-by-step diagnostic process for technicians. This manual is written in Chinese.
Covers: Error ID: 66116: Unified Cooler - Critical Flow Rate · Water Pump CB threshold definition · Electrical Phase is disconnected · External water valves are not fully open · Water filter is clogged · Water pipe quick connectors are not properly attached
Latest Unified manuals
Unified FB10000 Cooler Critical Flow Rate Troubleshooting Manual
Service Manual 11 pages · 1 MB · ZHTroubleshooting guide for Error ID 66116 on Unified FB10000 Cooler, covering water pump, phase, valve, filter, pipe, sensor, and pump issues.
Which document do I need?
Service Manual
Disassembly, diagnostics and part numbers, for repair.
Questions answered in Unified manuals
What are the correct CB threshold settings for the water pump?
The CB threshold settings should be 6.3A for 50Hz and 8A for 60Hz.
From: Unified FB10000 Cooler Critical Flow Rate Troubleshooting Manual
How do I check if the water pump is receiving current?
Use an Ammeter to check connections TB_DIS 16,17,18. All three TBs should receive current.
From: Unified FB10000 Cooler Critical Flow Rate Troubleshooting Manual