TianNeng DSI5152 Motor Protection and Measurement Device User Manual

The TianNeng DSI5152 motor protection and measurement device manual provides overview, specifications, installation, operation, and maintenance instructions.


TianNeng DSI5152 Motor Protection and Measurement Device User Manual - cover page
Brand
Beijing天能继保电力
Category
Other device
Document type
User Manual
Language
Chinese
Pages
46
File format
PDF
File size
1.2 MB
Updated
01 October, 2026
MD5 checksum
459D664F290601E6CD8C2C02C1A64296

About this manual

The DSI5152 is a motor protection and measurement device designed for 3 kV ~ 10 kV medium‑high voltage asynchronous motors. It can be installed locally in a switchgear cabinet or mounted on a panel and complies with IEC 61850 modeling requirements for smart grid applications.

The unit features a high‑performance CPU, dual Ethernet interfaces, a large LCD screen with up to 18 programmable indicator lights, and extensive protection functions such as differential, over‑current, over‑voltage, and fault recording. It operates in temperatures from –10 °C to +50 °C, with storage limits of –25 °C to +70 °C, and meets strict insulation and electromagnetic interference standards. This manual is written in Chinese.

What's inside

  • Overview
  • Applicable Range
  • Main Functions
  • Technical Parameters
  • Rated Parameters
  • Power Consumption
  • Output Contact Capacity
  • Working Power Supply
  • Protection Current and Voltage Ranges
  • Environmental Conditions

Specifications

Rated DC voltage220 V or 110 V (order specified)
Rated AC voltage (Uₙ)100 V (or 100/3 V)
Rated AC current (Iₙ)5 A or 1 A (order specified)
Frequency50 Hz
Power consumption (DC path)< 10 W normal, < 15 W during operation
Output contact capacityDC 220 V, 5 A (non‑arcing)
Working power supply tolerance± 20 %
Protection current range0.1 Iₙ ~ 20 Iₙ
Protection voltage range1 V ~ 140 V
Operating temperature-10 °C ~ +50 °C
Storage temperature-25 °C ~ +70 °C
Relative humidity≤ 95 % non‑condensing

Frequently asked questions

What voltage levels is the DSI5152 suitable for?

It is suitable for medium‑high voltage asynchronous motors rated from 3 kV to 10 kV.

What are the rated DC input voltage options?

The device can be powered by either 220 V or 110 V DC, as specified on the order.

What is the operating temperature range of the device?

It can operate from –10 °C up to +50 °C.

How many programmable indicator lights does the front panel have?

The front panel provides up to 18 programmable indicator lights.

Download PDF (1.2 MB)