Thermo King TriPac Power Inverter service bulletin covering operation, GFCI testing, fault codes, and diagnostic procedures for technicians.
This Thermo King service bulletin assists technicians in operating and diagnosing the TriPac Power Inverter. It includes important operating information, notes, diagnostic routines, fault code diagnostics, and diagnostic flowcharts.
The document covers inverter operation, status LED indications, Ground Fault Circuit Interrupter (GFCI) receptacle testing, checking input voltage and output power, and fault codes E01 through E08 with corrective actions.
| Under-voltage warning threshold | Battery voltage less than 11.0 Vdc |
|---|---|
| Under-voltage shutdown threshold | Battery voltage less than 10.5 Vdc |
| Over-voltage shutdown threshold | Battery voltage greater than 15.5 Vdc |
| AC standby transfer threshold | AC standby power falls below 90 Vac |
| Erratic operation threshold | AC standby power falls below approximately 107 Vac |
A red LED means the power inverter is turned on and a fault condition exists; the inverter output is shut down.
Turn the power inverter off and back on to clear a fault code.
The GFCI receptacle has been improperly wired; check and repair wiring as required.