User manual for the TECH EU-MW-1/230 wireless controller module: installation, manual mode, pairing, factory reset, technical data and alarms.
This user manual describes the EU-MW-1/230 (MW-1/230) wireless module made by TECH STEROWNIKI II Sp. z o.o. The module switches a potential-free contact when it receives a message from the main controller, so it can switch on a boiler, pump or valve actuators depending on the main controller. It communicates wirelessly and can work with up to 4 devices at the same time.
The document covers safety rules, device description and installation, manual mode, registration and advanced registration of devices, restoring factory settings, technical data, alarm behavior when communication is lost, and the EU Declaration of Conformity. It states that the device should be installed by a qualified electrician and that the power supply must be switched off before any work on the controller.
| Supply voltage | 100-240V / 50-60Hz |
|---|---|
| Operating temperature | 5°C - 50°C |
| Resistive load | < 10 A |
| Maximum power consumption | < 1 W |
| Operating frequency | 868 MHz |
| Maximum transmitting power | < 25 mW |
It can cooperate with 4 devices at the same time, and at least one device must send a signal for the contact to be activated.
After pairing is started on the MW-1/230, the pairing option in the main controller must be activated within 2 minutes, otherwise the attempt fails.
Communication is carried out every 4 minutes; without communication the receiver automatically disables the heating device contact after 15 minutes.
Press and hold the Manual mode button for 10 seconds until the two outermost control lights start flashing, then press the Pairing button.