Installation, operating and maintenance instructions for the Singer Model 26 Flow Stabilizer, including port connections and restriction sizing.
The Singer Model 26 is a low flow stabilizer used on Model 106/206-PR pressure reducing valves and other valves that require low flow stabilizing. It stabilizes the main valve by providing relatively unrestricted closing speed and controlled opening speed.
The document gives installation connections for Model 106/206-PR, restriction sizing by valve size, and on-valve and off-valve adjustment procedures, including cleaning and air-bleeding notes.
| Valve size 1/2" to 2" restriction | 1/16" |
|---|---|
| Valve size 2-1/2" to 4" restriction | 3/32" |
| Valve size 6" and larger restriction | 1/8" |
| Port 1 connection on Model 106/206-PR | Bonnet of Main Valve |
| Port 2 connection on Model 106/206-PR | Inlet of Pilot Valve |
| Port 3 connection on Model 106/206-PR | Inlet of Main Valve |
It is a low flow stabilizer used on the Model 106/206-PR pressure reducing valve and other valves that require low flow stabilizing.
Loosen the locknut and turn the adjusting screw counterclockwise until pulsing is dampened, then lock the locknut.
A 1/8-inch restriction is required in the line to Port 3.
Port 1 connects to the main valve bonnet, Port 2 to the pilot valve inlet, and Port 3 to the main valve inlet.