SensorData HT-912-T-01 Reference Bottle Calibration Manual

Instruction manual for SensorData HT-912-T-01 reference bottles used to calibrate HVAC relative humidity probes via 1-point and 2-point procedures.


SensorData HT-912-T-01 Reference Bottle Calibration Manual - cover page
Brand
SensorData
Category
Monitoring Equipment
Document type
User Manual
Language
English
Pages
2
File format
PDF
File size
637 KB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
1A33AE5C55AD434313D82206B775E6AF

About this manual

The document provides an instruction manual for SensorData reference bottles (HT-912-T-01) used to check and calibrate relative humidity transmitters. It lists five bottle types with saturated salt solutions at 12%, 33%, 55%, 75%, and 90% RH, each with a specific type number. The manual includes lifetime guidelines, handling precautions, and temperature compensation notes.

Two calibration procedures are detailed: a standard 2-point calibration using 12% and 90% bottles with zero and span adjustments, and a quicker 1-point field calibration using either 75% or 90% bottle with zero adjustment only. Both require pre-stabilization and approximately 3-hour stabilization periods. References to NBS and PTB standards are cited.

What's inside

  • Test Certificate
  • Checking Relative Humidity Transmitters
  • Life Time
  • 2-Point Calibration Procedure
  • 1-Point Calibration Procedure
  • Cautions and References

Specifications

Reference Bottle 12%RHType 101447
Reference Bottle 33%RHType 101448
Reference Bottle 55%RHType 101449
Reference Bottle 75%RHType 101450
Reference Bottle 90%RHType 101451
LifetimeApproximately 2 years with careful handling
Pre-stabilization TimeMinimum 1 hour at ambient temperature
Stabilization Time for CalibrationAround 3 hours

Frequently asked questions

How long should reference bottles be pre-stabilized before calibration?

Reference bottles must be pre-stabilized for a minimum of 1 hour at the present ambient temperature before use.

What is the expected lifetime of the calibration bottles?

The bottles have a lifetime of approximately 2 years depending on careful handling, provided the salt solution remains saturated with visible crystals and water.

What should you do if the salt solution in a bottle is not saturated?

If the bottle is fully filled with water, the salt is not saturated and the bottle should be replaced; if dry salt appears, refill with distilled water to about 40% capacity.