Instruction manual for SensorData HT-912-T-01 reference bottles used to calibrate HVAC relative humidity probes via 1-point and 2-point procedures.
The document provides an instruction manual for SensorData reference bottles (HT-912-T-01) used to check and calibrate relative humidity transmitters. It lists five bottle types with saturated salt solutions at 12%, 33%, 55%, 75%, and 90% RH, each with a specific type number. The manual includes lifetime guidelines, handling precautions, and temperature compensation notes.
Two calibration procedures are detailed: a standard 2-point calibration using 12% and 90% bottles with zero and span adjustments, and a quicker 1-point field calibration using either 75% or 90% bottle with zero adjustment only. Both require pre-stabilization and approximately 3-hour stabilization periods. References to NBS and PTB standards are cited.
| Reference Bottle 12%RH | Type 101447 |
|---|---|
| Reference Bottle 33%RH | Type 101448 |
| Reference Bottle 55%RH | Type 101449 |
| Reference Bottle 75%RH | Type 101450 |
| Reference Bottle 90%RH | Type 101451 |
| Lifetime | Approximately 2 years with careful handling |
| Pre-stabilization Time | Minimum 1 hour at ambient temperature |
| Stabilization Time for Calibration | Around 3 hours |
Reference bottles must be pre-stabilized for a minimum of 1 hour at the present ambient temperature before use.
The bottles have a lifetime of approximately 2 years depending on careful handling, provided the salt solution remains saturated with visible crystals and water.
If the bottle is fully filled with water, the salt is not saturated and the bottle should be replaced; if dry salt appears, refill with distilled water to about 40% capacity.