Instruction and operation manual for the SEC Millennium Hawk infrared hydrocarbon gas detector, covering specifications, operation, calibration, and…
The SEC Millennium Hawk is a microprocessor-based infrared hydrocarbon gas detector that continuously monitors combustible hydrocarbon gases and vapors within the Lower Flammable Limit. It provides a continuous 4 to 20 mA output and is suited for harsh environments.
This manual covers specifications, general description, operation, calibration, maintenance, parts list, drawings, unit status flash codes, and unit error codes.
| Available gases | Methane, Hexane, Jet A, Toluene, Ethane, Diesel, Ethanol, P-Xylene, Ethylene, Gasoline, Methanol, Tert-Butyl Acetate, Ethylene Oxide, Green Earth, Butane, MEK, Propane, DF 2000, Hexane |
|---|---|
| Detection method | Diffusion; optional sample draw requires a minimum of 1 liter per minute flow rate |
| Output (analog) | 4-20 mA (source type), maximum 1000 Ohm load at 24 VDC supply voltage |
| Response time | Standalone T50 < 5 seconds, T90 < 10 seconds; connected to 3100/3120 T50 < 6 seconds, T90 < 11 seconds |
| Construction | 316 stainless steel or 6061 aluminum (anodized) |
| Accuracy | +/- 3% LEL from 0 to 50% LEL; +/- 5% LEL from 51 to 100% LEL |
| Operating temperature rating | -40 to +70 C at 0 to 99% RH (non-condensing) |
| Operating pressure | 11.6 PSIA to 17.4 PSIA |
| Operating voltage | 24 VDC; operating range 18 to 32 VDC measured at the detector head |
| Power consumption | 3.6 Watts maximum |
| Current draw | At 24 VDC: 85 mA average, 150 mA peak; at 18 VDC: 135 mA average, 200 mA peak |
| Weight | 5 lbs (2.3 kg) stainless steel; 2 lbs (0.9 kg) aluminum |
| Approvals | Explosion proof (pending): Class I, Division 1, Groups B, C and D, Temp T5; combustible gas performance C22.2 60079-29-1 (pending); UL 2075 methane 0-100% LEL only; IP 66 rating; installation category Cat. I, pollution degree 2 |
| Warranty | Two years on materials and workmanship |
It can be calibrated for most hydrocarbons, including the gases listed in the manual, provided a calibration gas is available.
It provides a continuous 4 to 20 mA output (source type), with a maximum 1000 Ohm load at 24 VDC supply voltage.
The operating temperature rating is -40 to +70 C at 0 to 99% RH (non-condensing).
No. Due to the nature of IR technology, O2 is not required to sense gas and its concentration does not affect the reading.