The Santak PT 1-3K UPS User Manual provides safety, installation, operation, maintenance and specification details for the UPS.
This manual introduces the PT 1-3K UPS series, covering product overview, environmental protection, and key features such as double‑conversion online design, ABM® battery management and communication interfaces. It also explains safety symbols, handling of the sealed lead‑acid battery, and environmental storage requirements.
Detailed sections guide users through installation (rack or tower), wiring, communication ports, operation modes, fault and alarm handling, and regular maintenance. The final chapters list technical specifications, dimensions, weight, and warranty information. This manual is written in Chinese.
| Output Power | 1 kVA/1 kW (PT1K), 2.2 kVA/2.2 kW (PT2.2K), 3 kVA/3 kW (PT3K) |
|---|---|
| Output Voltage | 200‑240 V (adjustable) |
| Output Frequency | 50 Hz or 60 Hz (auto‑sense or fixed) |
| Input Voltage | 100‑276 VAC |
| Input Current | 6 A (PT1K), 12 A (PT2.2K), 16 A (PT3K) |
| Battery Voltage | 48 V (PT1K), 72 V (PT2.2K/3K) |
| Battery Capacity | 7 Ah (PT1K/2.2K), 9 Ah (PT3K) |
The UPS is covered by a three‑year free warranty and replacement service.
Store the UPS with battery at temperatures between –15 °C and 40 °C.
When replacing the battery, you must use the same model and quantity as the original battery pack.