Leaflet for the R Protection Systems 2320 control panel that supervises and controls one fire suppression hazard, with features, releasing devices and specs.
The 2320 is a low cost control panel from R Protection Systems, a UTC Fire & Security company, that supervises and controls one fire suppression hazard. Microprocessor technology is used for reliability and field programmable versatility, and the unit is compatible with Fenwal FM-200 clean agent suppression systems. It meets the requirements of NFPA 72 and is approved for use in suppression systems covered by NFPA codes 12, 12A, 17, 17A and 2001.
The panel provides 14 indicating status LEDs and 5 diagnostic LEDs. Field programmable options include multiple time delays, 3 abort modes, single or cross zone operation, release circuit isolation and a second alarm relay. Two independent style "B" initiating circuits can be programmed for single or cross zone application, and the 24 Vdc power supply is provided for either 120 or 240 Vac input with electronic overload protection and a built-in battery charger. The leaflet closes with ordering information and specifications.
| Input Power | 120 or 240 Vac, 0.25 Amp maximum |
|---|---|
| Standby Current | 35 mA |
| Alarm Current | 200 mA |
| Auxiliary Power | 0.25 amps @ 24 Vdc in alarm only |
| Input Circuits | Two style "B", 50 ohms, 10K EOL |
| Output Circuit | One style "Y", 0.5 Amp @ 24 Vdc, 10K EOL |
| Relay Outputs | Two alarm, one trouble, form "C", rated 2 Amp @ 24 Vdc |
| Initiator Output | Up to six P/N 93-191001-001 or up to ten P/N 31-199932-004 |
| Time Delay to Discharge (detectors only) | Field selectable 0 to 30 seconds in 10 second increments |
| Standby Battery | Optional 1.2 AH batteries give 24 hours standby plus five minutes alarm |
| Nominal Dimensions | 13-1/4 in. H x 11 in. W x 2-5/16 in. D |
It supervises and controls one fire suppression hazard, and the control unit is compatible with Fenwal FM-200 clean agent suppression systems.
One or two 24 Vdc solenoid control heads such as P/N 890181 or P/N 48650001, or sets of electro-explosive initiators, for example up to ten P/N 31-199932-004.
Mode 1 holds the timer at 10 seconds and counts down upon abort release, Mode 2 resets the timer to its initial value, and Mode 3 holds at 10 seconds if actuated before the 2nd alarm (IRI).
The features list gives UL, FM, ULC, MEA and CSFM.