R Protection Systems 2320 Fire/Suppression Control Panel Product Leaflet
The 2320 is a low cost control panel from R Protection Systems, a UTC Fire & Security company, that supervises and controls one fire suppression hazard. Microprocessor technology is used for reliability and field programmable versatility, and the unit is compatible with Fenwal FM-200 clean agent suppression systems. It meets the requirements of NFPA 72 and is approved for use in suppression systems covered by NFPA codes 12, 12A, 17, 17A and 2001.
The panel provides 14 indicating status LEDs and 5 diagnostic LEDs. Field programmable options include multiple time delays, 3 abort modes, single or cross zone operation, release circuit isolation and a second alarm relay. Two independent style "B" initiating circuits can be programmed for single or cross zone application, and the 24 Vdc power supply is provided for either 120 or 240 Vac input with electronic overload protection and a built-in battery charger. The leaflet closes with ordering information and specifications.
Covers: Description · Features · Indicating Status and Diagnostic LEDs · Programmable Options and Abort Modes · Initiating and Input Circuits · Releasing Devices
Latest R Protection Systems manuals
R Protection Systems 2320 Fire/Suppression Control Panel Product Leaflet
Product Leaflet 2 pages · 1 MB · ENLeaflet for the R Protection Systems 2320 control panel that supervises and controls one fire suppression hazard, with features, releasing devices and specs.
Questions answered in R Protection Systems manuals
What is the R Protection Systems 2320 control panel used for?
It supervises and controls one fire suppression hazard, and the control unit is compatible with Fenwal FM-200 clean agent suppression systems.
From: R Protection Systems 2320 Fire/Suppression Control Panel Product Leaflet
Which releasing devices can the control unit activate?
One or two 24 Vdc solenoid control heads such as P/N 890181 or P/N 48650001, or sets of electro-explosive initiators, for example up to ten P/N 31-199932-004.