Installation and cartridge change-out guide for Parker Hannifin's VF-61 filter housing, including safety, flow, and pressure specifications.
This document provides step-by-step installation instructions for the Parker Hannifin VF-61 filter housing, including safety precautions, connection details, and cartridge change-out procedures. It specifies that the housing is for liquid service only and includes guidelines for differential pressure monitoring and O-ring replacement. The guide also covers cartridge selection based on application type and includes warnings for specific fuel types.
| Connections Size | 1-½" Female NPTHousing |
|---|---|
| Housing Pressure Rating | 150 psi |
| Differential Pressure Limit (Aviation Fuel) | 15 psi |
| Differential Pressure Limit (Other Applications) | 25 psi |
| Flow Rate (Diesel Fuel) | 15 to 50 gpm |
No, the VF-61 is for liquid service only. Do not use or leak test with compressed air or other gases.
Use a Viton® O-ring instead of Buna-N for fuels that cause excessive swelling.
The differential pressure should not exceed 15 psi; replace the cartridge if it does.
Tighten all bolts to 33 ft-lbs, alternating in a crisscross fashion.