This manual covers the installation, wiring diagrams, parameters, and technical specifications for the Nanjing New Power Electric Co., Ltd. G Series Single…
The document provides a comprehensive guide for the G Series Single Channel Isolator, which converts current or voltage signals with galvanic isolation between input, output, and power supply. It supports HART communication and is designed to interface with systems such as DCS and PLC. The manual details various configurations including single/double outputs and sink modes.
| Power supply rated voltage | 18 V DC ~32 V DC (Recommended: 24 V DC) |
|---|---|
| Input resistance (Current) | approx. 50 Ω |
| Accuracy | ± 0.1% F.S |
| Response time | ≤ 2 ms |
| Temperature drift | 40 ppm/ ℃ |
| Dielectric strength | ≥ 1500 V AC |
| Operation temperature | -20 ℃ ~ +60 ℃ |
| Power dissipation (single output) | 1.3 W (at 24 V DC) |
The recommended voltage for operation is 24 V DC.
Yes, the current input isolator allows transmission of HART communication signals.
The device can operate in temperatures ranging from -20 ℃ to +60 ℃.